The nameplate of a 1,000 kVA transformer contains approximately 20 different items. Four of these items determine if a transformer will connect with your electrical distribution board; all others are used for record keeping. Proper ordering of the nameplate is essential so you will avoid making two of the most costly errors when working with transformers within this wattage range. These errors are ordering a transformer with an incorrect vector group and ordering a circuit breaker that will not perform under fault current levels that the transformer’s impedance provides.

Resposta rápida: for a transformer nameplate with a wattage rating of 1,000 kVA, the plate provides a long list of information for the end user, including (but not limited to): rated capacity; rated voltage and current; vector group (N-Y-D); frequency of operation; short-circuit impedance; cooling class; maximum temperature rise on insulation; maximum thermal withstand capability; range of wire tapping; total weight of the transformer; total weight of the type of oil used; and finally, which industry-recognized standard the transformer was built.

Placa de Identificação do Transformador 1000 kVA

Where the Plate Is, and Which Plate You Are Looking At

According to the nameplate of a transformer rated for operation at 11,000 volts and also rated for use on 433 volts, the high-voltage side of the transformer has an approximate full load current of 52.5 amps and the low-voltage side has an approximate full load current of 1,333 amps. Normal range for short-circuit impedance for transformers is 5.5 to 6.5 percent, and for transformers constructed in accordance with IEC 60076, the vector group marking will typically be Dyn11. The nameplate is typically located on the side of the tank (in the area where the lifting lugs are located) and is manufactured from stainless steel. The nameplate should not be removed or painted over; it serves as a legal document, as well as a label.

There is a rating plate on the electrical transformers that you should keep in mind. Most transformers will have 1, 2, or even 3 rating plates attached to the electric transformer. There is one main rating plate, which is typically stainless steel or anodized aluminum and riveted to the tank about eye height on the high voltage side, usually located between the lifting lugs of the transformer. When dealing with pad-mounted transformers, the rating plate will be facing you when you approach the opening door of the transformer box. However, with a pole-mounted transformer, the front of the transformer will be facing the street.

The next type of plate you will likely find on your electrical transformer will be the wiring diagram plate. The wiring diagram plate shows how the different windings are arranged as well as the tap points for each set of windings. There is also a test plate that is sometimes located on the tank, which contains information about the routine testing as well as the date of the test. If the electrical transformer has been manufactured in a larger size, you will often notice that a separate plate has been provided to include the oil data.

When you are looking for the rating plate on your electric transformer, you need to check the tank and not the radiator. The rating plate is attached to the tank of the electrical transformer with four rivets, and there will not be a sticker attached in this area. A sticker provides information in addition to what is found on the rating plate, as a riveted rating plate has the most importance. If a transformer has been refurbished, the rating plate may have been removed and transferred to the new tank, and the only link between the original manufacturer testing and the current tank would be through its serial number.

The Fields That Matter, With a 1,000 kVA Example

The Fields That Matter, With a 1,000 kVA Example

Field on the plate Example at 1,000 kVA Por que isso importa
Padrão IEC 60076 Which test regime and tolerances apply
Potência nominal 000 kVA Apparent power, not kW
Rated voltages 11,000 / 433 V Ratio and tap base
Rated currents 52.5 / 1,333 A Cable and breaker sizing
Connection symbol Dyn11 Paralleling and earth fault behaviour
Frequência 50 Hz Core design, no interchange with 60 Hz
Impedância de curto-circuito 6.0 percent Fault level at the secondary terminals
Resfriamento ONAN Continuous rating basis
Aumento de temperatura 60 K oil / 65 K winding Life at rated load
Nível de isolamento LI 75 / AC 28 kV Impulse and power frequency withstand
Tapping range Plus or minus 2 x 2.5 percent, off-circuit Voltage adjustment on the HV side
Peso total About 3,000 kg Lifting, transport, floor loading
Oil weight About 1,000 kg Spill plan, bunding, transport class

The top area of the nameplate shows an example using 1,000 kVA; this is important because it tells you which tests and tolerances apply to that test.

The frequency defines the transformer core design. The transformer cannot be interchanged with 60 Hz.

Rated Power: Why kVA and Not kW

It’s called kVA because a transformer rating is based on the full current of the transformer and the full insulation rating. It’s not based on the power factor of whatever is connected to the transformer.

At a power factor of 0.9, 900 kW can be delivered by a 1,000 kVA unit, while at 0.8 power factor, only 800 kW can be delivered; however, the windings of the unit would heat up the same amount regardless of which load is placed on it, as far as heating is concerned.

Therefore, you cannot convert a load schedule expressed in kW into a transformer rating when you do not know the power factor; and as a result, the figure on the nameplate is higher than what it would be if the power factor was known. In addition, when a plant has a total connected load of 950 kW and purchases a 1,000 kVA transformer, it has purchased a transformer that is running at an overload of 0.95 power factor, but at a comfortable level at 0.8 power factor.

The nameplate does not indicate a power factor because it is not defined by the transformer; the nameplate does indicate the current point, which is what is important to determine whether the cable and breaker are sized properly to accommodate the load. The explanation provided about the meaning of kVA transformer rating provides additional details regarding the conversion, and explains how the kW to kVA ratio will differ depending upon the overall load mix on the transformer.

Rated Voltage and Rated Currents: 11,000 / 433 V and 52.5 / 1,333 A

The rated voltage indicates the tap ratio and tap size of the transformer.

The rated current indicates how to size the cables and circuit breakers.

The rated current is calculated from the rated power (kVA) and the rated voltage (V) values provided on the nameplate; however, the kVA and V values on the nameplate are distinct from one another, as they represent current flowing through the windings of the transformer. The high voltage current will always be less than the low voltage current, since the two currents are multiplied or divided according to the turns ratio between the two voltages of the transformer. For example, a 1,000 kVA transformer divided by the square root of three multiplied by 11 (11,000 V or 11 kV) represents high voltage current of 52.5 A, whereas a low voltage transformer will have a rated current of 1,333 A at 433 V.

These two values explain the majority of the total cost of the transformer installation. A 52.5 A cable is considered a small cable, and a breaker rated at 63 A is applicable to it. A 1,333 A cable consists of 4 to 6 parallel runs of 240 mm² copper, and the breaker used for this application is rated for a frame of 1,600 A and a trip of 1,250 A. In this case, the transformer is treated as a single line item, while the low-voltage connection will consume the majority of the cost to install the equipment.

The figures on the nameplate indicate the rated voltage and rated power. However, when the tap position is at minus 5 percent, both the secondary voltage and available low-voltage current will rise accordingly; therefore, the breaker size is determined based on the maximum current flowing through it at the lowest tap position, not the nominal tap position. Therefore, if a transformer at minus 5 percent is rated to deliver a maximum of 1,400 A at 433 V nominal, then the breaker sized at exactly 1,333 A would nuisance trip when it would normally be able to handle an overload of approximately 1,600 A.

Impedance The Percentage That Decides the Breaker

Impedance: The Percentage That Decides the Breaker

Short-circuit impedance is described in percentage terms. For small distribution units, the percentage typically ranges from 4 percent to 6 percent and from 5.5 percent to 6.5 percent for 1,000 kVA. The short-circuit impedance for a transformer is calculated as the voltage (in percent) required to produce a short-circuit fault on the secondary.

This impedance will affect the amount of fault current. For instance, a 1,000 kVA, 433 V transformer with a 6 percent short-circuit impedance has a three-phase short-circuit at the secondary bus bar of approximately 24 kA. In comparison, a 4 percent short-circuit impedance transformer will provide approximately 36 kA of fault current, and thus, requires a different class of breaker with a different busbar rating and a different arcing flash calculation. This is the reason that impedance should be considered during the purchasing process instead of being included in the construction drawing, which is created after the order has been placed. When purchasing a transformer, a buyer specifying a low (impedance) value to improve voltage regulation will result in a higher fault (current) level and will be charged more for their switchgear. On the other hand, if a buyer specifies for a higher (impedance) value in order to reduce the fault (current) level, the results will be improved voltage regulation (compared to that of a transformer with a low impedance) and the transformer will operate at a higher temperature during motor starting.

IEC 60076-5 states that each transformer declared with an impedance tolerance. The plate figure represents the declared value instead of a maximum guaranteed value. A transformer that is declared at 6 percent may test at 5.4 percent, and will therefore have a fault (current) level that is increased by 11 percent. When building substation transformers, we declare the tested impedance on our routine test reports, as the plate value alone is insufficient for performing a protection study.

Vector Group: What Dyn11 Tells You

Dyn11 indicates the earth fault and parallel behaviour of the circuit breaker.

The connection symbol consists of two parts. The first part (the letters) describes the winding connections as they relate to the high voltage side of the transformer, (D = Delta, Y = Star) or the lower case letter relates to the low voltage side. The second part of the connection symbol has an ‘n’ and denotes that a neutral has been taken from the low voltage side. The number indicates the phase shift between the phasors (high and low voltage) using the clock method, and will be expressed in multiples of 30 degrees.

Dyn11 is the standard configuration for distribution transformers: Delta on the high voltage side, star with neutral on the low voltage side, and 30 degree lag. In delta/Star transformer connections, the delta winding traps the 3rd harmonic currents and keeps them from becoming part of the network. The star point provides a neutral point for the low voltage system.

The Clock Numbers on transformers are critical to determine if they can be paralleled. Two transformers with different clock numbers cannot be paralleled. Two transformers with the same clock number but different impedance are not parallelable either — the load will be shared in inverse proportion to their impedances rather than their kVA ratings. Therefore, if a plant has an existing 1000 kVA transformer and adds another 1000 kVA transformer next to it, both transformers must have the same clock number and both must match each other in terms of impedance to share the load properly. The same is true when adding additional transformers to existing installations; for that reason, records of the Clock Number for each transformer should be kept on file.

Cooling Class and Temperature Rise

The ONAN cooling class is defined as Oil Natural / Air Natural (i.e.: oil flows by natural convection and the radiator cools by ambient air). This is the most common rating for distribution transformers (see section 4.1.1) and is what the continuous rating is based off of.

The ONAF cooling class is the same as the ONAN cooling class except that it has fans in the oil tank. The ONAF cooling class increases the kVA rating of the same tank by 25–40% by using fans for cooling. For example, an ONAF transformer that has the following data: ONAN/ONAF = 1000/1250 kVA, is a transformer that is rated at 1000 kVA in the ONAN cooling class and can be operated in the ONAF cooling class at 1250 kVA with the fans in operation. The failed fan conditions must be taken into account when designing a protection scheme for the ONAF transformer.

Temperature rise is stated separately for the oil and windings, typically it is 60 K and 65 K. These temperatures are the rises above ambient temperature when operating at rated load; these temperature rises are directly related to the life of the insulation. An ONAN transformer that operates continuously 10 K above its rated temperature rise will only go through approximately half of the insulation life. Thus, the ambient conditions are very important for the performance of transformers, and transformers installed in poorly ventilated areas will exceed their rated design temperature, even at their maximum rated load. In addition to that, tap changers and their ranges are also very important.

Tap Changer: Off-Circuit or On-Load, and the Range

Most distribution transformers have off-circuit tap changers installed in the high voltage winding, and these have a range of +/- 2 x 2.5 percent in five different positions. At the time of commissioning, the tap changer is set to match the supply voltage that is present at that time, and it remains in that position throughout the life of the transformer. Off-circuit tap changers are used when the transformer is de-energized (if you have an oil-filled transformer, you would need to remove the access cover and move the tap links inside the tank).

On-load tap changers perform the same function while the transformer is energized and typically cost 15 to 30 percent of the total cost of the transformer. On-load tap changers are specified where the supply voltage has a large enough fluctuation to be impactful on the process being served by the transformer, particularly in the case of transmission or industrial applications, which are not typically seen in distribution applications.

The manufacturer will indicate on the nameplate of the transformer which type of tap changer is used and the total range of that tap changer. A transformer with a tap changer that has a range of +/- 2 x 2.5 percent would be able to correct a voltage variance of 5 percent because the tap changers can be used in combination to make the correction in two steps, which is sufficient for most distribution systems. In the case of a transformer that is serving a facility at the end of a long feeder that has a voltage drop of 9 percent, the tap changer would not be able to make the necessary corrections without either using a wider range or employing some other means of correcting the problem, as indicated on the nameplate.

Losses, Efficiency and the Figures That Are Not on the Plate

The rating plate for a transformer will not provide no-load loss and load loss values. They are two important factors in determining the cost of running a transformer. The values appear on the routine test certificate; if price quotes from two suppliers differ by 10%, this is the first information that should be requested.

In Europe, as part of the EcoDesign Directive, the maximum allowable no-load loss for a 1,000 kVA liquid-immersed distribution transformer is approximately 1,100 watts and the maximum allowable load loss is approximately 10,500 watts. A transformer with these values will have a difference of almost 1,700 watts at full load compared to a transformer that meets the above values, and a typical 1,000 kVA distribution transformer will run for approximately 6,000 hours per year (about 10,000 kWh of electricity annually).

For industrial customers who pay a premium rate for electricity, the difference in energy costs will repay the premium you paid for a low-loss transformer in approximately five to eight years, while the transformer will continue operating for approximately 30 years. Customers who compare only the price of a transformer are comparing only the purchase price and ignoring the majority of the transformer’s total cost, which is the cost of the energy consumed by the transformer.

Weights and Dimensions: The Transport Constraints

A 1,000 kVA ONAN distribution transformer has a total weight of approximately 3,000 kg, of which approximately 1,000 kg is oil and approximately 1,300-1,700 kg is core and windings. The weight of the transformer (total weight) and oil weight is listed separately on the rating plate. The total transformer weight determines the type of crane used to lift the transformer and how much weight the floor will support. The oil weight determines the transport classification and size of the volume of the spill containment area. The overall view of the 1,000 kVA unit is approximately 2,100 mm long by 1,350 mm wide by 1,750 mm high, with bushings added to the overall height of the unit. The dimensions may change with the location of the radiator and tank shape; therefore, the drawing is the governing document rather than the nameplate.

A 1,000 kVA unit is more like a lorry-sized load than a pallet-sized load, and the access route to the installation location (plinth) must be verified before the order is placed. If a unit arrives at a doorway that is 50 mm too narrow, it will be sitting on a pallet outside while a wall is removed.

How Plates Differ Between Manufacturers and Standards

While an IEC nameplate and an IEEE nameplate contain the same data, the data is ordered differently and uses different verbiage; a person looking at a comparison between a European quotation and an American quotation will see two different documents describing the same product.

An IEC nameplate has Dyn11 for the connection symbol and the impedance is given as a percentage. An IEEE nameplate has the same vector relationship expressed in the same clock notation, but the basic impulse level (BIL) is called out as a single value like 95 kV or 110 kV; the impedance is given with a tolerance band. The temperature rise for an IEEE nameplate is given as a single value along with the average winding rise; sound level in decibels is often included on an IEEE nameplate but may not be included on any IEC nameplate. There are two designations of rated power, but the voltage classes of the units differ in that the IEC voltage classes are classified according to 11, 22 and 33 kV, whereas ANSI units are classified according to voltages from 2.4 to 34.5 kV with secondary voltages of 480 V and 600 V. Therefore, a kVA rating of the same size and capacity will not interchange between IEC and ANSI units due to the differences in design that clearly identify the IEC versus ANSI units, as indicated in the first two lines of the labels.

The details of the design differences may be seen by referring to a worked example of the same kVA rating at a higher kV class voltage, e.g. a 1,000-kVA transformer at 35 kV; the insulation class, impedance, weights and dimensions are increased for the higher kV transformer.

Item IEC 60076 plate IEEE C57 plate
Connection symbol Dyn11 Dyn11, usually with the vector stated in words
Nível de isolamento LI 75 / AC 28 kV BIL 95 kV, single figure
Impedância Percentage, declared value Percentage with a tolerance band
Aumento de temperatura Oil and winding separately, in kelvin Average winding rise, single figure
Nível de som Often on the test certificate only Usually printed on the plate, in dB

What the Plate Does Not Tell You

What the Plate Does Not Tell You

Here are examples of information that is not included on the rating plates of either the IEC or IEEE kVA transformer. Five essential documents exist for buyers that do not exist on the transformer rating plate:

  • all losses are contained in the test certificate
  • impedance tolerance is specified in the relevant standards
  • sound levels are contained in the test certificate and sometimes shown as a separate label.

The enclosure’s IP rating is displayed on the label of the enclosure. The IP rating is determined based on the national standard for industrial equipment, and the guidelines for determining an IP rating for an industrial equipment transformer state that the IP rating for the enclosure and the nameplate for the transformer are two distinct items. The test report containing the results of the routine test that demonstrates that the unit’s nameplate is consistent with the unit’s actual performance when it is tested is provided with all transformer shipments.

The last item is where you must hold firm. The nameplate is showing you what was designed by the manufacturer, while the results of the routine test report provide information on the actual performance of that one specific serial number. If a manufacturer sends you a type test report rather than a routine test report, you only know about the design details, and not about the actual unit in the shipping package.

Perguntas Frequentes

Where is the nameplate located on a transformer rated at 1,000 kVA?

The nameplate is typically located on the tank wall, at a location that will be visible to personnel, usually on the high-voltage side of the transformer, often situated between the lifting lugs. If the transformer is mounted on a pad, the nameplate will be located behind the door of the unit; if the transformer is on a pole, the nameplate will face the nearest highway. The nameplate is normally made of either stainless steel or anodised aluminum with riveted-on rivets; there will likely also be an additional smaller nameplate that describes the winding and tap configuration of the transformer.

What do the various current ratings on a transformer rated at 1,000 kVA mean?

The rated currents indicate the maximum current that can be passed through the transformer windings, stated for the respective rated voltages. The 1,000 kVA transformer has two specified current ratings: 52.5 A on the high voltage side and 1,333 A on the low voltage side. The maximum value determines how cable and breakers are sized. The low voltage rating will increase at the extreme tap position; therefore, the breakers are sized on the extreme or maximum values compared to nominal values.

O que significa Dyn11 em uma placa de identificação de transformador?

Dyn11 indicates a delta connection on the high voltage side of the transformer and a wye (also known as a star) with a neutral point on the low voltage side. The phase rotation between the high and low voltage sides is 30 degrees lagging. Dyn11 is a standard connection for transformers used for distribution. The reason is that the delta connection captures all third harmonic currents and the wye connection provides a neutral point in the low voltage network.

Is the nameplate impedance the guaranteed impedance?

The nameplate impedance is the declared value according to IEC standards, which allows for some tolerance. For example, a transformer that declares 6 percent may test at 5.4 percent, which can raise the short circuit fault level at the secondary by approximately 11 percent. When performing a short circuit protection coordination study, always use the tested impedance listed on the routine test certificate.

Referências

Conclusão

On a 1,000 kVA transformer nameplate, four decisions were made and recorded. The rated power provides information regarding apparent power delivery. The current ratings indicate what cable and breaker sizes are required; among them, the low voltage current rating is critical because it is associated with additional costs. The impedance provides switchgear rating information for fault interruption capability; the vector group provides information regarding the ability to connect the new transformer in parallel with an existing transformer.

The remaining information provides additional supporting details: The insulation rating provides voltage class verification; the cooling class and temperature rise establish continuous rating; the tapping range accounts for supply errors; and the transformer weights provide capacity for crane. The only two pieces of information not included on the nameplate are loss measurements and test impedances; these are available on the routine test certificate and are key to distinguishing where you are purchasing a design versus an actual transformer unit.