To many people, like myself, the only way we may describe these types of equipment is “the round ones.” These round components are actually porcelain-tubed electrical insulators supporting overhead lines of electric current within substations, as well as various transformer components.
Schnelle Antwort: the three primary types of round components in a substation are bushings, insulators, and corona rings. Bushings are used to pass high-voltage lines or conductors through a grounded barrier. Insulators separate and hold conductors from the ground, while also providing mechanical support for insulators holding conductors at various elevations (through the use of a series of insulators). Corona rings provide a mechanism for reducing electrical stress on insulated equipment. The professional name for bushings, insulators, and corona rings are bushings, post insulators, suspension insulators and corona rings, respectively. When ordering insulators, it is essential to have the specific type clearly stated on the order, otherwise, it will be ambiguous.
This article contains descriptions of each type of component, their mechanical and electrical functions, reasons why components are circular, an explanation of how the number of discs required is determined and a summary of where components originate.

The short answer: three components people call “the round things”
The bushing is a passage for the conductor through a grounded barrier. The bushing acts as an insulated passage for the conductor to keep insulation intact while crossing the grounded barrier (i.e., transformer, switchgear, wall). The bushing does not provide support, and it is not a separator. The bushing acts as an insulated door for a wire.
The insulator is a support and separator for the conductor. The post insulator holds the busbar up for the transformer. The suspension insulator (from gantry to conductor) holds down the conductor from the gantry. In normal operation, neither carries current. Both carry a mechanical load while holding the voltage.
The corona ring is not a support nor a separator. The corona / grading ring is a metal torus bolted around a fitting, designed to reshape the electric field in the area around the fitting, and it is designed to keep the torus away from contact with the live conductor at the point of maximum field strength.
| What you see | Bauteil | Carries current | Carries load | Typischer Standort |
|---|---|---|---|---|
| Porcelain cylinder on a transformer lid | bushing | yes | Tatsache | transformer tank, switchgear wall |
| Stack of discs hanging in a string | suspension insulator | Tatsache | yes | gantry, tension tower |
| Ribbed column holding a busbar | post insulator | Tatsache | yes | busbar support, isolator base |
| Bare metal torus above a fitting | corona / grading ring | Tatsache | Tatsache | top of bushings, surge arresters |
Bushings: the round part the conductor passes through
From the discussion above, one can conclude that bushings are the components that give substations their appearance.
In an oil-filled transformer there are 3 bushings that rest on the lid of the transformer, and each has a hollow porcelain or composite column with a conductor in the middle of the column. The purpose of the bushings is to maintain the insulating gap between the conductor and transformer tank.
The tank is grounded (earthed) and the conductor is at line potential (about 72kV), with separation between the two elements of approximately a few hundred mm or less. If there were no bushings, the conductive path from transformer tank to conductor would be through the oil surface (flashover) or through air (flashover). Both pathways would tend to flashover at a fraction of the rated voltage, leading to a potential transformer explosion.
Most high-voltage bushings (greater than 72kV) are of the condenser-type design, which typically consists of a porcelain insulator; an oil-impregnated paper core surrounded by layers of aluminum foil that acts as successive capacitors that exponentially zero-grades the voltage through the entire insulating material between the insulated conductor (center) and flange. This design provides multiple smaller capacitance and tan delta test taps at the flange, which allows for the measurement of capacitor condition, as well as providing the main point for diagnosis of possible condition issues.
A bushing has no prior indications before catastrophic failure due to rising tan delta, increasing moisture within the paper core, or through internal transformer pressure buildup. Such failures pose one of the few dangers within the complete substation environment because the sudden catastrophic failure of a bushing may cause an explosion, which will destroy the transformer tank. Bushings are scheduled for testing, and therefore, it is common to keep a spare set. Bushings are located on the transformer that provides output power, and a failure of a bushing means that the transformer will no longer be in service regardless of the condition of the windings. The arrangement of the components on a typical oil-immersed distribution transformer is clearly illustrated. A 20kV oil-immersed distribution transformer contains the bushings, the tap changer, and the lifting lugs on the top cover, and the spacing of the bushings is determined by the voltage class.
When considering the round shape of the bushing, an electric field is produced. In the case of a round or cylindrical shape with smooth sides, the electric field is nearly uniform along its length. However, if the bushing has a square cross-section, the electric field is concentrated at the corners, where the radius of curvature is low. The electric field strength in the corners of a square bushing may be two to three times the average electric field strength. This concentration of the electric field creates conditions for partial discharge to occur.
The ribs on the bushing provide an additional design consideration. Each rib provides a longer creepage distance for moisture to travel across the bushing. In wet or contaminated conditions, the smooth cylindrical shape of the bushing has a much lower flash-over voltage rating than the ribbed type.
Post insulators and suspension discs
Post insulators are the columns with ribs at their tops that are used to support busbars, connecting blades, and cable terminations. Post insulators are subject to a combination of bending and compressive loads. The bending strength, not the voltage level, is the determining value when it comes to post insulator specifications. An electrically adequate post insulator can snap under a short-circuit condition if the cantilever loading capability is not sufficient. Suspension insulators consist of individual components, known as discs, that make up a string. Each disc has its own cap and pin and the string is constructed from multiple uniform discs. A typical 110 kV string consists of seven to nine discs, while a typical 220 kV string consists of 13 to 16 discs. The number of discs used is determined by the amount of pollution present at the site and not by the voltage.
The mechanical strength rating of a suspension insulator is expressed as the total mechanical load on the suspension insulator (e.g., 70, 120, or 160 kN) and is based on the type of work being performed, while the electrical strength rating is measured in wet power frequency units. In terms of materials, glass suspension insulators have one significant advantage over porcelain suspension insulators: if a glass suspension insulator breaks, it loses its insulating properties but will remain attached to the string, so the failure is evident from the ground. In contrast, a porcelain suspension insulator that is cracked may continue to provide service until the next inspection. This difference in the failure characteristics of the two materials leads many electric utilities to use glass suspension insulators for transmission lines and porcelain suspension insulators for substations.
Corona rings: the metal circles above the fitting
Corona rings are metallic rings located above the attachment point (the attachment point is located above the string or connection).
The torus is located at the top of high-voltage bushings or surge arresters and serves as a grading ring. Grading rings do not provide insulation and do not transmit mechanical loads; grading rings merely alter the shape of the electric field; this prevents the air surrounding the attachment point from breaking down.
The area of maximal electric field at the bushing is where the electrical conductor exits the porcelain. When a tube or ring is used to protect a transmission line from corona discharge, the diameter and tube size helps increase the area over which the concentration of the voltage field is dispersed, and therefore the magnitude of the voltage field at which corona is created; this helps keep the local field below the corona inception level when a correctly sized tube or ring is used. Furthermore, while the corona itself is not harmful, the electrical erosion of the surrounding insulator caused by corona creates a significant amount of radio frequency interference (RFI), audible noise, and also creates ozone that can deteriorate rubber-based (e.g., elastomeric) insulation and dielectric materials.
Each pole that has a decent-sized ring or tube (the diameter of the fitting surrounding the ring and the height at which the tube is installed) has a corresponding voltage rating. Changing the tube size to one that is not the same voltage (i.e., higher voltage or lower voltage) does not provide additional protection and may negatively impact the distribution of electrical energy along the wire and can potentially be harmful. This is why the rightful voltage class ring or tube is included with either the bushing or arrester, rather than being an accessory item.

What the round things on poles are
A pole-mounted transformer (PMT) is typically located on the upper portion of a pole. The PMT consists of a sealed cylinder, or tank, that has bushings mounted on top to connect to the overhead wires. Although the PMT is not an insulator, it is often confused with an insulator by people who observe it.
The small round objects, or pin insulators, are located on cross-arms adjacent to the PMT; the string-like configuration of discs (a “suspension set”) serves as a connecting link between the PMT and the distribution line. The surge arrester (the white or grey cylinder mounted adjacent to the PMT) is designed to protect the PMT from lightning surges and related energy that travels along the electrical lines.
The colored markers attached to the high voltage wire between spacers indicate to pilots that an aircraft must obtain clearance before flying near the line; the rings or small discs at the point of suspension provide a means of reducing vibration.
The terms a buyer actually uses, and why it matters
This could also be misinterpreted by procurers because in English the word “insulator” can refer to three separate products. When a person may ask for “insulators for the 33 kV substation”, they could be asking for either post insulators, suspension discs, or bushings, and all three of these answers would be appropriate. The Russian term ввод is the correct term for bushings and is not interchangeable with изолятор, which translates to insulator in English; similarly, in Chinese the term 套管 is bushing and 绝缘子 is insulator. In a written specification when written across multiple languages, the part number and drawing take priority over terminology.
For purchasing, the following four items will eliminate any confusion that could occur: each item will specify the function (passage/ support/ suspension), the type of electrical insulation (voltage rating/ insulation class), mechanical rating and creepage distance for that type of insulator. This will allow the supplier to accurately quote the appropriate product despite any mislabeling on their part.
Materials: porcelain, glass, composite, epoxy, and paper
Porcelain is traditionally used; it is strong in compression; it remains stable/usable outdoors for decades, and its surface remains smooth and clean from deposits caused by pollution. The downside of porcelain insulators is that they are brittle and may break and not be visibly discernible until viewed from below. Tempered glass is generally used for suspension discs; however, it has a higher dielectric strength per millimetre than any other type of insulator and because it fails in a visible manner, it is easier to inspect, although it does come at an increased cost in both weight and the possibility of producing fragments upon failure.
Composite insulators are constructed of a fibreglass core with a silicone rubber shed. Porcelain and tempered glass electrical insulator materials have been the standard for years, but currently some manufacturers are offering composite type (silicone + FRP) electrical insulators which have many relative advantages over the previous two materials. Compared to porcelain and tempered glass, composite insulators are generally lighter in mass, provide better resistance to vandalism, operate satisfactorily in areas where airborne pollution is heavy, and typically composite insulators are manufactured with a hydrophobic (water repellent) coating on their outer surfaces. The hydrophobic coating is a factor in the performance of the composite insulator because while it provides some protection against moisture intrusion, it does not provide long term tracking resistance against moisture and UV radiation. The most significant issue affecting moisture and UVA tracking resistance in a composite insulator is the quality of the bond between the shed and the core. The bond quality can differ between manufacturers greatly. Epoxy cast resin is used to manufacture indoor switchgear bushings and post insulators, where the material can be cast to form a compact shape, while oil impregnated paper (OIP) is used within condenser bushing cores to control field grading between the coils and the OIP.
There are many types of materials currently available for use as the primary insulator in transmission and distribution electrical systems. As described earlier in this document, Porcelain, Tempered Glass and Composite Electrical Insulators are generally considered high strength materials with a high level of reliability. However, each material has both advantages and disadvantages as listed below.
| Material | Main use | Stärke | Weakness |
|---|---|---|---|
| Porcelain | post insulators, bushings | long life, stable surface | brittle, cracks hidden |
| Tempered glass | suspension discs | visible failure, high strength | weight, fragments |
| Composite (silicone + FRP) | transmission, polluted sites | light, hydrophobic, vandal resistant | bond quality varies |
| Epoxy cast resin | indoor switchgear | compact, precise shape | limited to indoor or protected |
| OIP paper | condenser bushing core | controlled field grading | moisture sensitive |
Creepage and why the number of discs matters
Creepage distance is the distance measured along an insulated surface from the live part (bus or conductor) to earth. Creepage distance is specified for each unit of line voltage. Each line voltage is different due to environmental conditions (pollution levels). Creepage distance is measured at the following values depending on pollution level at the site:
| Pollution level | Creepage distance |
|---|---|
| Light | 25 mm/kV |
| Mittel | 31 mm/kV |
| Heavy | 35–40 mm/kV |
The level of pollution (airborne) is determined by the environment and is not a personal preference of the Specification Writer. If a substation is located near a cement plant, in a coastal environment where it experiences exposure to salt spray, or in a location with a high concentration of conductive-type-dust; then you need the higher figure. The consequence for using an inappropriate number would be that you may have flashover during the foggy conditions rather than at the time of commissioning.
The meaning of this number is that it is also the reason that two insulators may be rated differently even though they are both the same height. The taller insulator has many more ribs, which will provide a longer creepage path compared to an insulator that is shorter and has widely spaced ribs that have been moulded deep into the insulator and have the appearance of being more robust. However, when the creepage path is analysed, the taller insulator has the higher creepage rating because it has a longer creepage path. The drawing provided in the standard gives the creepage percentage rating for each insulator, regardless of appearance.
Most of the packages used for substation equipment will have the same creepage requirement stated on the information sheet for each of the insulators used for that package, so that when the bills of material are created, they will list the packages based on pollution level, and then by voltage level, which is true for substation equipment within the same high voltage substation equipment range.
Where to buy, and what a set costs
There are three avenues to purchase these insulators and you cannot interchange them. The first one is from the original equipment manufacturer. When you are purchasing a bushing for a transformer, you purchase the bushing from the transformer manufacturer, and they guarantee that the bushing fits and that the field grading is correct. You can purchase the bushing separately from an existing transformer, but in that case, you are required to know the drawing, and the flange dimensions. The second group is the bushing and insulator component manufacturers; they each have a dedicated factory that manufactures these components and sells them direct to transformer manufacturers as well as electric utility companies. They can provide a spare set based on the original part’s drawing; this is typically the only way to acquire a replacement or upgraded version. The third type of manufacturer is the MRO distributor, which stocks common ratings of both bushings and insulators for immediate delivery at an extra cost of approximately 30% to 50% above standard pricing.
| Artikel | Spannung | Indicative price (USD) | Lieferzeit |
|---|---|---|---|
| Porcelain bushing, transformer | 12–24 kV | 60–250 each | 1–3 weeks |
| Composite bushing, transformer | 36 kV | 180–500 each | 2–4 Wochen |
| Condenser OIP bushing | 145 kV | 4,000–18,000 each | 8–20 Wochen |
| Post insulator | 12 kV | 30–120 each | 1–3 weeks |
| Suspension disc (70 kN class) | per unit | 6–25 each | 1–4 weeks |
| Corona ring | matching 145 kV | 150–600 each | supplied with the fitting |
These pricing indications are for budgetary purposes only and are not representative of what you would pay if you were to place a purchase order. The broad bands within the price ranges reflect the individual manufacturer’s cost to produce the insulators and bushings; there will be significant differences between an insulator supplied with only a Declaration of Conformity vs an insulator supplied with a full set of test documentation including routine test reports and type test certificates (the difference being approximately 20%-40% on average).
For orders in which insulators are included as part of an equipment package (e.g., in conjunction with other components such as transformers), it is more practical to purchase the insulators/insulator assemblies together as opposed to separately. By purchasing the assembly as a whole, it is much easier for the equipment designer/manufacturer to coordinate the interface of all of the components (the dimensions of the mounting flanges, creepage level, and corona ring) as opposed to each component having separate suppliers and potentially conflicting requirements; it is not uncommon for this to occur in the case of high voltage electrical equipment packages.
Manufacturers worth knowing
Three established names in insulator manufacturing are NGK Insulators (Japan), Sediver (France – glass) and Lapp Insulators (Germany – porcelain and composite). These companies comprise most of the global supply of transmission-class discs and posts and their catalogues serve as the reference for disc dimensions and mechanical class.
Trench Group is well respected as the manufacturer of bushings, while Hitachi Energy and ABB offer bushings as part of transformer and switchgear packages. The type-test documentation is what a utility specification usually cites for bushings. In many distribution-level projects, utilities will have two options: Either a regional factory that can supply an equivalent rating with a routine test report at a lower cost, or a classic global brand that has a longer history of field use. Both options are acceptable, and the deciding factor will be how the utility’s standard specification identifies a brand as an acceptable source. A mandated list will uniquely identify the source of supply.
When insulators are subcomponents of a transformer or switchgear order, the assembly supplier has responsibility for supply of the insulator(s), and the component range of insulators is provided under “Electrical Substation Components“.

What to check when a set arrives
Four checks identify most issues, and none of these checks necessitate laboratory testing. The first check is the creepage distance compared to the drawing. Measuring the creepage distance is simply a matter of measuring from the edge of the insulator along the creepage distance with a piece of string, and even a creepage distance that is as little as ten percent short of what it should be, will cause the pollution class of the installation to be reduced.
Flange and bolt circle dimensions are the second most important aspect of bushing compatibility to the tank flange; if they do not match (i.e. are not the same), gaskets can not be installed and fluid can leak from the bushing to the tank. Condition of sheds is another critical aspect to the overall quality of the bushing. Chipped sheds on porcelain are not merely cosmetic; chips create a moisture trap and point where the electric field concentrates, which creates the potential for failure under most specifications. Test documentation is also crucial to bushing design. Normally, a unit test report is created for bushings; the type testing report provides the design-based information for the bushing and does not provide any testing information specific to the bushing. This same documentation logic applies to current transformers, whereas the numerous designs and schedules on the high-voltage current transformers document how the schedule of tests is attached to the individual unit and not to the batch of units it was tested with.
Häufig gestellte Fragen
What are the round things on electric poles?
Typically, those are pole mounted transformers; they are sealed cylindrical tanks rather than insulators. The little circular objects on the crossarm just above the pole are pin insulators; the white cylinder that is bolted to the side of the transformer is a surge arrester that protects the transformer from lightning.
What are the types of insulators used in substations?
There are multiple styles of electrical insulators used in substations. These styles include post insulators for mounting bus bars, suspension insulators to support cables between towers, bushings to allow conductors to pass through grounded barriers, and enclosed apparatus insulators used within switched electrical gear and instrumentation transformers. Of these, the first three types tend to be visible and, therefore, will be what you see when looking at a substation from outside of the perimeter fence.
What are the circle things on power lines?
The circular coloured balls attached to high-voltage transmission lines are marker balls that warn pilots of the presence of the transmission lines below them. The smaller circular rings that fall within the anchor/support section of the transmission line serves as a vibration damper to help reduce the aeolian vibrations created by wind-induced movement. In contrast to those balls and rings, an insulator does not conduct electricity, so neither item should be mistaken for an insulator.
What does an insulator do in a substation?
Electrical insulators support live electrical components and separate them from energized portions of the operation and the ground as well as hold the electrical bus bars or overhead conductors in place; during normal operation, however, the insulator itself carries no current. The way an insulator works is determined primarily by the creepage distance, the mechanical load(es) and, depending on the use of the insulator as a long-term insulator, the levels of pollutants present in the environment.
Why is a bushing different from an insulator?
Yes, the primary distinction is that bushings hold conductor cables inside of them, whereas insulators do not carry current in any manner. This key difference between bushings and other forms of electricity-related tooling affects how bushings and other forms of electrical insulating products are designed, tested and, ultimately, how they fail when exposed to environmental conditions. Bushings fail when subjected to the presence of moisture and/or paper deterioration and by contrast, insulators fail primarily through surface flashover or mechanical breakage.
Referenzen
- Trench Group — High Voltage Bushings and Coil Products
- NGK Insulators — Transmission and Substation Insulators
- Sediver — Toughened Glass Insulators
- Lapp Insulators — Porcelain and Composite Insulators
- Hitachi Energy — Bushings and Substation Equipment
Fazit
In conclusion, as we noted previously, the round or cylindrical items visible in the substations associated with electric utilities serve three distinct functions. First, as stated, bushings contain conductors travelling through the center of the bushing and serve the purpose of transferring electricity through themselves as normal insulators do. The next round object is the insulated supports; and lastly, the third reason round objects exist within substations relates to the corona rings and their role in shaping and forming the field surrounding the bushing; these do not touch anything.
As such, the importance of specifying the correct terminology associated with bushings (i.e., name, function, voltage class, mechanical rating and creepage distance) is paramount for determining the precise insulator components supplied when requested by the electrical utility customer.