Blog

Transformer Rectifier Machine

A transformer rectifier machine is an integrated assembly that consists of a transformer, which converts AC to a suitable voltage for electrolysis, and a rectifier, which converts the AC voltage to a DC voltage using diodes or thyristors. In general, the rectifier will include a filter(s) and a control section built into the same enclosure as the transformer.

Quick answer: the transformer side of the machine will be built according to IEC 61378-1 using high impedance, harmonic rated winding and often a phase-shifting secondary winding. The type of rectifier includes both an AC/DC (direct current) and an AC/AC (alternate current) version. An AC/DC rectifier will produce a DC output voltage with varying ripple and regulation depending on the pulse number that is usually specified as a six-pulse (the baseline) or twelve-pulse (most commonly used in industry).

Transformer Rectifier Machine

Definition: What the Term Actually Covers

It is important to note that while the transformer and rectifier are sold by different companies, they must be compatible to create a working transformer/rectifier machine. Separating the individual parts into packages makes it difficult for users to know if they are compatible, as companies do not share this type of information. Therefore, electrolysis plants, cathodic protection systems, and DC substations buy transformer/rectifier machines instead of components. The definition of a converter transformer in IEC vocabulary includes both a transformer, and rectifier assembly in terms of what constitutes a transformer rectifier unit (TRU). In general usage, the terms rectifier, TR unit, and transformer rectifier all refer to the same type of product; and the name stated on the quote generally indicates which industry benefits from the converter transformer product.

There are essentially three different types of configurations available. The first configuration consists of one tank which houses both the transformer and the rectifier and is oil-immersed, commonly used for low-level DC applications up to several thousand amps. The second style consists of a transformer separated from the rectifier enclosed within separate housings with busbars connecting the two. This configuration is employed in high-output DC applications where high-output diodes require separate cooling means. The third configuration consists of an indoor/dry-type transformer with a rectifier mounted directly on top of it. This configuration is appropriate in locations where oils are prohibited.

All the above configurations allow for a complete assembly of the TRU to be made for DC applications. The TRU is not a standard distribution transformer; it has been designed so that the excitation voltage selected by the transformer will produce the required DC output, the resistive/inductive impedance will limit fault current through the diodes, and the winding configuration has been made so the transformer experiences a nonlinear voltage and current waveform. Compared to standard distribution transformers, TRUs are engineered and constructed differently to accommodate the differences between alternating and direct-current utility systems.

The Working Principle, Stage by Stage

The Working Principle, Stage by Stage

The primary winding, usually delta connected, receives the AC supply and also allows the triplen harmonics generated in the winding to circulate and remain within the winding, thus eliminating them from being reintroduced into the system. The voltage rating of the secondary is determined by the voltage needed at the load; however, since it is a 12 pulse machine, there are two windings on the secondary; one a delta winding, and the other a star winding. The two secondary windings are 30 electrical degrees apart.

The rectifier section converts the incoming AC voltage to pulsating DC. In a diode-based machine, the path of conduction is fixed, and the output of the machine is in sync with the availability of voltage on the supply side. In contrast to this, a thyristor-based machine will utilise the firing angle of the thyristors to control the output voltage; thus providing a controllable regulated DC voltage and a means of limiting available output current at the expense of having an inferior low output power factor.

Following the rectification stage there are either a capacitor or inductor filtering device. The size of the filter will depend on how much ripple is able to be tolerated by the load. Electroplating loads can tolerate several percent ripple; no ripple exists within a DC drive application; and no tolerable ripple exists with a magnet supply. This necessitates the incorporation of either a large series choke or an active filter into the magnet supply.

From an ideal 6 pulse bridge, the DC voltage produced from the secondary line voltage will be equal to 1.35 times the voltage on the secondary line. It is important to remember this factor, because it will provide the basis for understanding many of the sizing arguments associated with the rectifier system. For example, with a 400 V secondary line with a rectifier, the output voltage will be approximately 540 V DC with no consideration given to losses. However, based on losses and other factors, DC output voltage will be lower by the sum of diode drop, commutation overlap, and transformer regulation losses. In total, these losses are predicted to be in the range of 4–8 percent when operating at full load.

The transformer has a greater influence on the operation of the machine than the rectifier; therefore, the three parameters of the converter transformer differ from those of an equivalent distribution transformer unit.

Why It Is a Transformer First and a Rectifier Second

The transformer has a greater influence on the operation of the machine than the rectifier; therefore, the three parameters of the converter transformer differ from those of an equivalent distribution transformer unit.

Impedance — The impedance of a distribution transformer ranges from 4% to 6%; however, the impedance of a converter transformer can range from 6% to 12% (or more). The reason for the difference in impedance is due to the fact that in the event of a short on the DC side the diodes of the rectifier will carry the complete fault current of the transformer. A higher impedance than that of a distribution transformer is the most economical way to keep the fault current below the surge-rating limit of the diodes. However, this creates poor voltage regulation, which must be controlled by the control system.

Harmonic rating — The winding of a converter transformer carries a substantial amount of harmonic current, and that harmonic content can produce eddy current losses in the conductors and stray losses in the tank which are not considered in a 50 Hz distribution transformer. Consequently, either the rating of a converter transformer is de-rated or it is constructed with transposed conductors and a non-magnetic tank shielding. This construction is one of the reasons that converter duty kVA has a higher cost than distribution duty kVA; the difference in the two types of duty is not based on marketing.

Tap range — Electrolysis plants have a constant current operating condition. The cells in an electrolysis plant will age, and therefore, the secondary voltage will need to increase over the life of the installation. Machines that have a plus or minus 10% tap range with fine step adjustments can provide a method for maintaining a constant current during cell voltage drift. An operator unable to produce the needed energy supply must compensate for this deficiency by running the supply at higher temperatures than normally would be required.

Number of Pulses Six, Twelve, Twenty-Four and What That Buys

Number of Pulses: Six, Twelve, Twenty-Four and What That Buys

The pulse number refers to the number of direct current (DC) pulses created in a DC power source over the course of a full supply cycle. As described above, this is determined by the number of rectifier legs and the relative phase shift between the two secondaries connected to the transformer. As the pulse frequency of the DC source is a function of the number of rectifier legs connected to the transformer, it has the most significant impact on ripple frequency, and therefore on the ripple value and total harmonic distortion (THD), of all choices available to the designer.

Configuration Ripple frequency at 50 Hz Typical ripple factor Current THD at the supply Where it is used
6-pulse 300 Hz About 4.2 percent Around 30 percent Small plating lines, single drives
12-pulse 600 Hz About 1.4 percent Around 10 percent Most industrial DC supplies
24-pulse 1,200 Hz About 0.35 percent Around 3 percent Large electrolysis, weak grids

Using the above as a guide, two six-pulse groups connected to one another via a delta and star secondary, and phased at 30 degrees, yield a twelve-pulse configuration. The fifth and seventh harmonics within the supply’s current are cancelled in the primary winding, and this cancellation reduces the supply current’s THD by a factor of three compared to a six-pulse configuration. Similarly, a twenty-four-pulse configuration is obtained by using four 15-degree phase-shifted six-pulse groups rather than two, and these configurations cancel additional harmonics—the eleventh and thirteenth.

In summary, twelve-pulse DC supplies cost 15–25% more than six-pulse DC supplies, yet eliminate the need for tuning filters to mitigate fifth and seventh harmonics. In some situations, such as a weak network where the utility limits the harmonic current that can pass, a twelve-pulse machine is a lower-cost solution than filter banks plus the larger switchboard needed to carry the same harmonic current.

Harmonic Duty, K-Factor and the Winding That Survives It

Many manufacturers use the term Harmonic Duty or K Factor to describe how much harmonic current a transformer can endure before overheating. K-13 and K-20 rated transformers are designed to accommodate the harmonic spectrum created by six-pulse rectifiers, which create more harmonic current than a sine wave of the same RMS value. When a transformer experiences distorted current, it generates more heat than it would for a sine wave of the same RMS value because eddy current losses (which increase with the square of the frequency of the current) cause an increase in temperature.

When converters are in use and supplying power to loads that create additional harmonic currents, the design of the transformer needs to take into consideration how much extra heat will be generated, rather than relying solely on the K Factor rating. This can be done through higher flux margins within the core, transposed or continuously transposed conductors in the low-voltage windings, and a tank using aluminum or stainless steel shielding to keep stray harmonic currents from the walls.

When analyzing bids for converters and transformer designs, the buyer should ask for loss calculations based on the actual harmonic spectrum produced by the converter, rather than simply applying the K Factor or K Factor Ratings to a rated sine-wave load.

The difference in performance between a converter transformer rated for a 100 K temperature rise at a 4% harmonic content and one rated for a 30% THD without increased cooler design will show itself as a winding running an additional 15 to 20 K over the nameplate temperature rise.

The three numbers which define the DC side of the system, are defined by three different conditions.

DC Output: Ripple, Regulation and the Load Characteristic

The three numbers which define the DC side of the system, are defined by three different conditions.

Rated DC Current — Continuous current at an ambient and cooling environment.

Rated DC Voltage — The voltage at that continuous current. Open Circuit Voltage — higher due to the regulation, typically 5% to 10% higher. To run a process that requires 100 V at full load, the machine must have an open circuit value in the range of 105 V to 110 V, in order for the process to run properly, meaning it must have sufficient voltage to accommodate the amount of load required by the process.

Ripple, stated in percentage of the DC value at rated load, will increase at light load due to the ineffectiveness of the filter. Therefore, a machine specified with 2% ripple at full load will have 6% ripple at 10% load. This is significant for a plating rectifier since most of its time is spent at low loads or currents.

Regulation is the difference in voltage between no load and full load, expressed as a percentage of voltage drop. A diode rectifier has a fixed regulation set by the impedance of the transformer, while a thyristor rectifier has an output voltage that remains within a fraction of a percentage until it reaches its maximum firing limitation. The type of rectifier chosen depends primarily on whether the process requires a constant current or a constant voltage; therefore, it is beneficial to specify which is needed in the request for quotation.

Rectifier, Inverter and Transformer: Three Terms That Are Not Interchangeable

Three separate, non-interchangeable terms for rectifier, inverter and transformer are:

  • A rectifier converts AC to DC
  • An inverter converts DC to AC
  • The function of a transformer is to change the voltage of alternating current (AC) while leaving the frequency of that AC unchanged. In other words, the type of power delivered from a transformer to other devices that use power is always alternating current (AC).

A transformer rectifier provides both the function of a transformer and a rectifier in one unit. This is also the reason why there is a terminal marked DC on the transformer rectifier; it cannot replace the function of a transformer in a distribution board. Often customers looking for a DC service make the mistake of ordering a transformer with an item added.

In terms of comparison, the most meaningful way to compare transformers and transformer rectifiers is with the variable speed drives, which have rectifiers on the front and inverters on the other side of the drive. Variable speed drives receive alternating current (AC) power, convert that AC power to direct current (DC) power using a DC bus, and then supply alternating current (AC) power at a frequency different from the input frequency. The transformer rectifier provides DC power at the DC bus; however, the load on the DC bus is DC power, therefore the transformer rectifier design does not include an inverter on the output.

The difference between transformer rectifiers and variable speed drives is primarily the method of connecting devices to the DC bus; therefore, transformer rectifiers only deliver one type of DC power. The most useful point to keep in mind is that only one of the three types of devices has DC connections.

Impedance: The Number That Protects the Diodes

Impedance is the parameter that distinguishes the two types of transformer rectifiers, and it is where the most common quoting error occurs. When a direct current (DC) bus is shorted, the current at the fault location will be limited by the impedance of the transformer and the impedance of the DC bus. The time it takes for a fuse or breaker to open and stop current flow creates a window of opportunity for diodes to handle surges. A semiconductor fuse will usually take a few milliseconds to operate while a case molded breaker will usually take longer. A 10 times rated diode that has a surge of 8.3 milliseconds cannot survive a fault that the transformer will allow through at 20 times the rating.

The practical range for a converter transformer is 6–12 percent. Impedance levels in a converter transformer are used to protect against fault currents at high DC ratings. Lower than 6 percent impedance makes it difficult to protect against fault currents. Greater than 12 percent the regulation of the transformer will degrade and the overall size of the transformer will become very large. If a DC current rating is very high, sometimes the impedance is split between the transformer and an external reactor, which is much more economical than having to build an extensive reactor into the winding of the transformer.

One important point that needs to be mentioned early on in an enquiry is that a customer who provides an impedance from their old distribution transformer will receive a transformer with insufficient capability to protect against their new process due to the specification of a high DC rating. It is critical that both numbers be specified together.

Cooling and Enclosure: ONAN, AN, AF and the IP Rating

Cooling and IP rating for enclosures follows the same terminology as any transformer, with only one additional terminology being added to it. Oil natural and air natural are ONAN. ONAN is the default form of cooling for oil immersed transformers rated up to several MVA. ONAF adds fans and increases the rating by 25 to 40 percent while using the same tank. AN is a dry type air natural transformer which can be used indoors, and is used in those applications where a cast resin transformer is acceptable. Also, the rectifier has its own thermal limit that is generally more restrictive than the transformer; the diode junction is limited to 125 to 150 °C, and the heatsink must be lower than that at a specified ambient temperature. In a sealed environment, the heatsink serves as the limiting factor, and therefore, the enclosure must include either a heat exchanger or an air-to-air cooler (a more expensive component than many end users anticipate).

Ingress Protection is the second decision when designing an enclosure; IP21 is generally sufficient for a clean plant room, but for outdoor equipment, IP54 is the minimum. In hot regions, any item rated IP55 or greater will require forced cooling since a sealed box cannot dissipate heat through convection alone.

The 10 kV dry-type transformer in the SCBH series represents a dry-type option for machines operated inside of buildings using cast resin windings, with no oil, and with an enclosure that can be configured according to the plant room’s allowable IP rating and temperature rise.

Where These Machines Are Used, and What Each Process Asks For

Where These Machines Are Used, and What Each Process Asks For

The six primary industries produce the majority of the demand and specify the associated performance characteristics. Electroplating and anodising applications require low voltage and high current, with loose ripple but very stable current control. Cathodic protection requires a consistent low-current output and remote user input, and most cathodic protection units are compact (air-cooled) devices that are typically housed in a cabinet located near a pipeline.

The table provides example voltages and currents, required pulse count, and control priority.

Process Typical DC voltage Typical DC current Usual pulse number Control priority
Electroplating 6 to 24 V 1,000 to 20,000 A 6 or 12 Constant current
Anodising 12 to 30 V 500 to 10,000 A 6 or 12 Ramp and hold
Cathodic protection 20 to 100 V 10 to 200 A 6 Stable output
DC drives 400 to 750 V 100 to 3,000 A 12 Fast current limit
Water electrolysis 100 to 1,000 V 5,000 to 40,000 A 12 or 24 Efficiency
Magnet and test supplies 10 to 200 V 100 to 2,000 A 12 or 24 Minimum ripple

Electrolysis and hydrogen production require very high current; therefore, the maximum efficiency is the most important criterion since these plants operate continuously. A 1% efficiency improvement on an installation rated at 50 MW results in a much larger dollar savings effect than does the price difference between two suppliers. Mining and haulage equipment must be ruggedly constructed, have a large ambient temperature range, and often have dual outputs in order to power two separate sections of an overhead line. Testing and magnet supplies require the least amount of ripple, and they are the one category where an active filter is economically justified. Transformers are used to convert AC electrical power to the direct current (DC) required by equipment for processing. Epoxy resin cast transformer technology provides many advantages for outdoor applications in high-volume production environments. However, specifying epoxy resin cast transformers correctly requires engineering input from the customer to determine several key parameters. By clarifying these parameters before contacting suppliers or requesting quotes, customers can get the most accurate quote possible for their specific needs, which results in a more cost-effective purchase and installation process.

The indoor half of this list is covered by epoxy resin cast dry-type transformers in the 10 kV class, which are designed for plating and testing facilities.

What to Put in an Enquiry So the First Quote Is Right

When placing an order for an epoxy resin cast transformer, there are six important pieces of information to provide:

  • The DC Current and Voltage produced at the process, separately stated for Maximum and Rated.
  • The AC Supply Voltage, Frequency and Phase Count, as well as the Fault Level at the Point of Connection.
  • The Duty Cycle, defined as Continuous, Intermittent, or Cyclic as well as the “on” and “off” times.
  • Required Regulation and Ripple expressed as a percentage.
  • Ambient Temperature and the location of the installation, either Indoor or Outdoor.
  • Harmonic Limit applied by the Utility, or a statement that there is no limit.

With these six items supplied to the supplier, an appropriate converter transformer can be sized, Pulse Number selected, Impedance set, and Cooling Class selected. If any of these six items are omitted from the request/quote, the supplier will be forced to make an educated guess about the duty cycle of the converter transformer in the quote, which will frequently result in the lowest-cost solution that will meet the minimum DC rating. It is this low-cost solution that will fail first in service. An industrial manufacturing solution developed by us provides a more economical alternative to purchasing the three separate elements instead of as an integrated solution due to the approach of combining the medium voltage feed, transformer and DC Distribution into one scope, eliminating three separate purchases and one single point of integration risk associated with three separate purchases.

FAQ

What are the main functions of Transformer Rectifiers?

They provide a controlled DC supply to the process from the AC network, at the voltage and current the process requires. The transformer provides voltage and isolation, and the rectifier converts the voltage to DC. The combination of the two is applied where the load is DC and the supply is AC (e.g. Electroplating, Cathodic Protection, DC Drives, Electrolysis, Magnet Supplies).

What is a Rectifier Machine?

In industry language it is “the complete system, not just the bridge”, consisting of converter transformer, rectifier stack, filter, control and protection and cooling all mounted on one frame/tank with the ONLY operator interface being the positive and negative DC terminals mounted on the outside.

What is the difference between Rectifiers and Transformers?

The transformer changes the AC voltage to any AC output voltage with the same frequency. The transformer rectifier changes AC to DC and cannot change the voltage by itself. The transformer rectifier combination does both, thus providing a DC output that cannot be produced by a transformer.

What is the purpose of the rectifier?

The purpose is to permit the flow of current in one direction only, converting an alternating supply into a direct supply. For example, in a DC power supply it means producing DC for a load; in a measurement circuit it has the same meaning, only at a smaller scale. While the conversion purpose is clear, voltage change is not the primary function and the two purposes are often confused since they are often referred to together.

References

Conclusion

A Rectifier Transformer Machine is two separate operations combined into one, where in many cases the transformer operation outweighs that of the rectifier operation. The importance of the converter is higher impedance/harmonic-rated windings and the tap range covering potential Drift of the process, thus giving a clear indication to end-users that this is a dedicated application and should have longer life than other types.

The pulse number option will have the largest consequence to the customer; for example, the twelve-pulse device costs between 15–25 percent more than a six-pulse device and eliminates the need for fifth- and seventh-harmonic filters, which often can be the least expensive alternative in weak distribution networks. Moreover, be aware that if you have the six enquiry items identified (DC Voltage and Current, Supply Specifications, Duty Cycle, Ripple, Ambient Location, Harmonic Top), then you will be able to provide the first quotation from where you will be able to build your machine.